Hyjet Stainless Steel Aisl304 Vertical Multistage Pump With VSD Controller 240V
Product Description
The product image shown is for illustration purpose only
Specifications
Pump Model |
Controller |
Power (kW) |
HP |
MAX FLOW L/Min. |
MAX HEAD (m) |
AMPS |
VOLTAGE |
CONNECTION Outlet (mm) |
Inlet |
PHASE |
HMV3-7-E1 |
E1 VSD Controller |
1.1 |
1.5 |
80 |
80 |
6.4 |
230 |
32 |
32 |
Single |
HMV3-9-E1 |
E1 VSD Controller |
1.5 |
2 |
80 |
103 |
7.7 |
230 |
32 |
32 |
Single |
HMV5-7-E1 |
E1 VSD Controller |
1.5 |
2 |
140 |
81 |
8.7 |
230 |
32 |
32 |
Single |
HMV5-10-E114 |
E114 VSD Controller |
2.2 |
3 |
140 |
114.1 |
11.9 |
230 |
32 |
32 |
Single |
HMV9-6-E114 |
E114 VSD Controller |
2.2 |
3 |
260 |
71.8 |
12.5 |
230 |
40 |
40 |
Single |
HMV9-7-E309 |
E309 VSD Controller |
3 |
4 |
260 |
83.3 |
5.8 |
415 |
40 |
40 |
Three |
HMV9-10-E311 |
E311 VSD Controller |
4 |
5.5 |
260 |
122 |
8.3 |
415 |
40 |
40 |
Three |
HMV18-4-E114 |
E114 VSD Controller |
3 |
4 |
360 |
47.9 |
5.7 |
415 |
50 |
50 |
Three |
HMV18-6-E311 |
E311 VSD Controller |
4 |
5.5 |
360 |
70.5 |
8.7 |
415 |
50 |
50 |
Three |
HMV18-9-E318 |
E318 VSD Controller |
6.6 |
9 |
360 |
106.4 |
12.7 |
415 |
50 |
50 |
Three |
 Application
- Designed for pumping clean non-loaded fluids for pressurising systems; heating and air conditioning; washing systems
Construction
- Pump Body: Stainless Steel AISl304
- Impeller: Stainless Steel AISl304
- Mechanical Seal: Ceramic/ Graphite< 6 Impellers
- Graphite / Silicone Carbide < 7 Impellers
- Liquid Temperature: -15 to 11 0c
- Max Operating Pressure: 8.5 bar< 6 impellers 14 bar< 7 impellers
- Motor: 2 Pole Induction
- with Thermal Protection
- Insulation: Class F
- Protection: IP44