| Controls: |
| Control variant: |
  |
AR |
| Level control: |
  |
YES |
| Analog input: |
  |
0/4-20 MA |
| Pulse control: |
  |
YES |
| Ext. Stop input: |
  |
Yes |
| Analog output: |
  |
0/4-20 MA |
| Output relays: |
  |
2 |
| Bus communication: |
  |
YES |
|
| Liquid: |
| Pumped liquid: |
  |
Water |
| Liquid temperature range: |
  |
0 .. 50 °C |
| Selected liquid temperature: |
  |
20 °C |
| Density: |
  |
998.2 kg/m³ |
|
| Technical: |
| Type key: |
  |
DDA 60-10 AR-PV/T/C-F-31U3U3IG |
| Max. Flow: |
  |
60 l/h |
| Max. flow in slow mode 50%: |
  |
30 l/h |
| Max. flow in slow mode 25%: |
  |
15 l/h |
| Min flow: |
  |
75 ml/h |
| Turn-down ratio: |
  |
1:800 |
| Approvals: |
  |
CE,CSA-US,NSF61,RCM |
| Valve type: |
  |
Standard |
| Maximum viscosity at 100 %: |
  |
150 mPas |
| Maximum viscosity in slow mode 50 %: |
  |
2000 mPas |
| Maximum viscosity in slow mode 25 %: |
  |
3000 mPas |
| Accuracy of repeatability: |
  |
1.5 % |
|
| Materials: |
| Dosing head: |
  |
PVDF (Polyvinylidene fluoride) |
| Valve ball: |
  |
Ceramic |
| Gasket: |
  |
PTFE |
|
| Installation: |
| Range of ambient temperature: |
  |
0 .. 45 °C |
| Maximum operating pressure: |
  |
10 bar |
| Installation set (Yes/No): |
  |
NO |
| Installation type: |
  |
No installation set |
| Pump inlet: |
  |
Conn.pack U3 (hose ID.19mm &.. |
| Pump outlet: |
  |
Conn.pack U3 (hose ID.19mm &.. |
| Max. Suction lift during operation: |
  |
3 m |
| Max. Suction lift during priming: |
  |
1.5 m |
|
| Electrical data: |
| Maximum power input - P1: |
  |
62 W |
| Mains frequency: |
  |
50 / 60 Hz |
| Rated voltage: |
  |
1 x 100-240 V |
| Enclosure class (IEC 34-5): |
  |
IP65 / TYPE 4X |
| Length of cable: |
  |
1.5 m |
| Type of cable plug: |
  |
Australia, New Zealand, Taiwan |
| Inrush current: |
  |
70A at 240V (35A/100V) for 2ms |
|
| Others: |
| Net weight: |
  |
6 kg |
| Gross weight: |
  |
7 kg |
| Colour: |
  |
RED |
| Country of origin: |
  |
FR |
| Custom tariff no.: |
  |
8413509060 |